Elevator Recall/Shutdown Matrix

Building Sprinklered
 
Building Location Location Sprinklered Recall Detection Elevator Recall Elevator Fireman's Hat Shutdown Detection Elevator Shutdown
Basement Lobby Yes Smoke Detector primary (1st floor) On None N/A
1st Floor Lobby Yes Smoke Detector alternate On None N/A
2nd Floor Lobby Yes Smoke Detector primary (1st floor) On None N/A
3rd Floor Lobby Yes Smoke Detector primary (1st floor) On None N/A
Machine Pit Yes Smoke Detector primary (1st floor)* Flash Heat Detector Yes**
Hoistway Pit Yes*** Pit Heat Detector higher of primary/alternate Flash None N/A
Hoistway Ceiling No None N/A N/A None N/A
Hoistway Ceiling No Smoke Detector**** higher of primary/alternate Flash None N/A
 
 
 
Building Not Sprinklered
Building Location Location Sprinklered Recall Detection Elevator Recall Elevator Fireman's Hat Shutdown Detection Elevator Shutdown
Basement Lobby No Smoke Detector primary (1st floor) On None N/A
1st Floor Lobby

No

Smoke Detector alternate* On None N/A
2nd Floor Lobby No Smoke Detector primary (1st floor) On None N/A
3rd Floor Lobby No Smoke Detector primary (1st floor) On None N/A
Machine Pit No Smoke Detector primary (1st floor)* Flash None N/A
Hoistway Pit No None N/A N/A None N/A
Hoistway Ceiling No None N/A N/A None N/A
Hoistway Ceiling No Smoke Detector**** higher of primary/alternate Flash None N/A
 
 
 
*Normally, primary is 1st floor and alternate is basement or 2nd floor; machine room recall alternate floor if machine room on primary floor
**Heat detectors in machine room to shunt trip electric power prior to sprinkler head within 2ft of pit floor
***Seperate pit heat detector not required by code because of pit sprinkler head within 2ft of pit floor
****By code, ceiling smoke detector permitted in unsprinklered hoistway only if required for smoke relief/exhaust