| Building Sprinklered |
| |
| Building Location |
Location Sprinklered |
Recall Detection |
Elevator Recall |
Elevator Fireman's Hat |
Shutdown Detection |
Elevator Shutdown |
| Basement Lobby |
Yes |
Smoke Detector |
primary (1st floor) |
On |
None |
N/A |
| 1st Floor Lobby |
Yes |
Smoke Detector |
alternate |
On |
None |
N/A |
| 2nd Floor Lobby |
Yes |
Smoke Detector |
primary (1st floor) |
On |
None |
N/A |
| 3rd Floor Lobby |
Yes |
Smoke Detector |
primary (1st floor) |
On |
None |
N/A |
| Machine Pit |
Yes |
Smoke Detector |
primary (1st floor)* |
Flash |
Heat Detector |
Yes** |
| Hoistway Pit |
Yes*** |
Pit Heat Detector |
higher of primary/alternate |
Flash |
None |
N/A |
| Hoistway Ceiling |
No |
None |
N/A |
N/A |
None |
N/A |
| Hoistway Ceiling |
No |
Smoke Detector**** |
higher of primary/alternate |
Flash |
None |
N/A |
| |
| |
| |
|
| Building Not Sprinklered |
|
| Building Location |
Location Sprinklered |
Recall Detection |
Elevator Recall |
Elevator Fireman's Hat |
Shutdown Detection |
Elevator Shutdown |
| Basement Lobby |
No |
Smoke Detector |
primary (1st floor) |
On |
None |
N/A |
| 1st Floor Lobby |
No |
Smoke Detector |
alternate* |
On |
None |
N/A |
| 2nd Floor Lobby |
No |
Smoke Detector |
primary (1st floor) |
On |
None |
N/A |
| 3rd Floor Lobby |
No |
Smoke Detector |
primary (1st floor) |
On |
None |
N/A |
| Machine Pit |
No |
Smoke Detector |
primary (1st floor)* |
Flash |
None |
N/A |
| Hoistway Pit |
No |
None |
N/A |
N/A |
None |
N/A |
| Hoistway Ceiling |
No |
None |
N/A |
N/A |
None |
N/A |
| Hoistway Ceiling |
No |
Smoke Detector**** |
higher of primary/alternate |
Flash |
None |
N/A |
| |
| |
|
| |
|
| *Normally, primary is 1st floor and alternate is basement or 2nd floor; machine room recall alternate floor if machine room on primary floor |
| **Heat detectors in machine room to shunt trip electric power prior to sprinkler head within 2ft of pit floor |
| ***Seperate pit heat detector not required by code because of pit sprinkler head within 2ft of pit floor |
| ****By code, ceiling smoke detector permitted in unsprinklered hoistway only if required for smoke relief/exhaust |